ASTM C1971-26

Current Revision
Standard Practice for Preparation, Testing, Calculation, and Reporting of Water Vapor Transmission Properties of Cylindrical Pipe Insulation Assemblies

Best Price Guarantee Oct 1, 2026 English 6 Pages

Sub Total (1 Item(s)) $ 0.00
Estimated Shipping $ 0.00
Total (Pre-Tax) $ 0.00

You own the digital copy of this edition

View in Library
or
ASTM International Logo

ASTM C1971-26

Standard Practice for Preparation, Testing, Calculation, and Reporting of Water Vapor Transmission Properties of Cylindrical Pipe Insulation Assemblies

PUBLISH DATE 2026
PAGES 6
ASTM C1971-26

1.1 This practice covers the preparation, testing configuration, calculation, and reporting of water vapor transmission properties of cylindrical pipe insulation specimens and pipe insulation assemblies tested in accordance with Test Methods E96/E96M, desiccant method.

1.2 This practice provides specimen preparation and calculation procedures for determining water vapor transmission rate, water vapor permeance, and, when applicable, water vapor permeability of cylindrical specimens tested by the desiccant method of Test Methods E96/E96M.

1.3 This practice provides requirements for the content of reports when this practice is applied.

1.4 Water vapor permeability shall be reported only for homogeneous materials having a wall thickness greater than or equal to 0.5 in. (12.7 mm), as permitted by Test Methods E96/E96M.

1.5 This practice applies only to specimens tested by the desiccant method of Test Methods E96/E96M.

1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. (See Table 1 of Test Methods E96/E96M.)

1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.

1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

5.1 Pipe insulation systems used on below-ambient-temperature piping are often designed to limit water vapor ingress and reduce the potential for condensation within the insulation or on the pipe surface.

5.2 This practice provides a common specimen configuration and calculation approach for comparing cylindrical pipe insulation materials and assemblies tested under the same Test Methods E96/E96M exposure conditions.

5.3 Preformed, closed-cell foam pipe insulation with inherently high water vapor resistance due to the closed-cell structure of the product is in many applications used without a separate vapor retarder jacket or facing. Such insulation is tested without attached vapor retarder and only with sealed joints.

5.4 Water vapor-permeable insulation materials may be tested with attached sheet, film, or fluid-applied vapor retarders when the vapor retarder system is intended to limit water vapor transmission through the assembly.

5.5 In some severe applications, closed-cell foam is used with an attached vapor retarder. In this case, the test result for the insulation and vapor retarder in combination is obtained.

5.6 The results from this practice are used for classification, product development and research, comparison of materials used in similar applications, quality control purposes, or combinations thereof. This test does not evaluate the water vapor transmission properties for all environmental conditions possible. Results obtained using this practice are specific to the test conditions and specimen configuration and should not be assumed to represent all service conditions.

Loading...