Specification for the installation and maintenance of low pressure gas installation pipework of up to 35 mm (R1<sup>1</sup><sub>4</sub>) on premises
This British Standard specifies the design, installation, commissioning and maintenance of gas installation pipework carrying 2nd and 3rd family gas of up to 35 mm (R 1¼) on premises, including residential park homes (2nd and 3rd family gas) and caravan holiday homes (2nd family gas) (see Table 1 and examples in Figure 1 to Figure 3; see also Figure 4).
NOTE 1 The principles of the standard can also be applied to the design, installation, commissioning and maintenance of gas installation pipework carrying 1st family gas.
NOTE 2 Annex A gives a method for calculating pipe sizes. Annex B discusses the sulfidation of natural gas installations, while Annex C summarizes the conclusions of a report on gas in intermediate floors. Guidance on determining whether an area can be deemed a “protected area” is given in Annex D. Requirements for LPG final stage regulator and safety devices are specified in Annex E. Annex F discusses the need for gas pipework design and installation for commercial installations to satisfy regulatory requirements regarding explosive atmospheres.
This British Standard is not applicable to:
service pipework and distribution systems;
pipework contained within an appliance;
bulk storage vessels;
LPG pipework installed in leisure accommodation vehicles and for accommodation purposes in vehicles in accordance with BS EN 1949;
boats, yachts and other vessels;
gas pipework supplying or within appliances having their own gas supply, such as mobile heaters; or
gas pipework supplying or within catering establishments covered by BS 6173.
Table 1 Pipework covered by BS 6891
| Gas type | Pipework | Maximum nominal diameterA) | Nominal operating pressure mbarB) |
|---|---|---|---|
| 2nd family (NG) |
Downstream of the primary meter installation, but not downstream of the inlet of any appliance isolation valve or the inlet of the self‑sealing connector of any flexible connection | R1¼ steel, DN 35A) |
21 |
| 3rd family (LPG) |
Downstream of:
|
R1¼ steel, DN 35A) |
37 (propane) 28 (butane) |
A) Dependent upon material type.
B) 1 bar = 105 N/m2 = 100 kPa.
NOTE Unless stated otherwise:
a) the diameter for pliable corrugated (stainless-steel) tubing refers to the inside diameter; and
b) the diameter for carbon, stainless-steel tubing, copper and polyethylene (PE) refers to the outside diameter.
Figure 1 2nd family gas installation with an internal meter

Key
| 1 | Service pipe | 7 | Appliance isolation valve |
| 2 | Primary meter installation | 8 | Appliance |
| 3 | Installation pipework | 9 | Part of installation within the scope of BS 6891 |
| 4 | Appliance connector | R | Regulator |
| 5 | Service isolation valve (where fitted) | M | Meter |
| 6 | Emergency control valve |
Figure 2 3rd family gas installation with cylinders

Key
| 1 | Service pipework | 6 | Appliance isolation valve |
| 2 | Installation pipework | 7 | Appliance |
| 3 | Appliance connector | 8 | Part of installation within the scope of BS 6891 |
| 4 | Cylinders | R | Regulator with over-pressure shut-off |
| 5</ |