This Standard Practice establishes the selection, specification, installation, materials, and testing of fixings and suspension systems for cable used to suspend pipe.
This Standard Practice establishes the allowable load values for cable suspensions when used to suspend pipe.
This Standard Practice presents the recommended practice for the suspension of pipe with cable for typically dry, indoor applications only.
This Standard Practice presents the recommended practice for the selection and application of cable with pipe operating (service) temperatures between -20 °F (-29 °C) and 200 °F (93 °C).
This Standard Practice establishes recommended procedures for the installation of up to NPS 6 (DN 150) pipe with loads not to exceed 715 lbf (3.19 kN) per suspension point.
This Standard Practice excludes any pipe which would typically be hung and supported via engineered supports.